Freelance Electronics Components Distributor
Closed Dec 25th-26th
800-300-1968
We Stock Hard to Find Parts

FRN-R-10

Part # FRN-R-10
Description FUSE 10A 250V DUAL ELEM - Bulk
Category FUSE
Availability In Stock
Qty 4
Qty Price
1 + $6.89838
Manufacturer Available Qty
Bussmann
  • Shipping Freelance Stock: 4
    Ships Immediately



Technical Document


DISCLAIMER: The information provided herein is solely for informational purposes. Customers must be aware of the suitability of this product for their application, and consider that variable factors such as Manufacturer, Product Category, Date Codes, Pictures and Descriptions may differ from available inventory.

0713 BU-SB13730 Page 1 of 3 Data Sheet # 1019
FUSETRON™ 250V Class RK5
FRN-R — 250Vac/125Vdc,
1
10-60A, Dual Element, Time-Delay Fuses
Description: Advanced protection, energy efficient Class RK5
dual element, current-limiting, time-delay fuses with optional
open fuse indication on select ratings.
Time-delay – 10 seconds (minimum) at 500% of rated current
(8 seconds for
1
10-30A sizes).
Catalog Symbol: FRN-R-(amp) (non-indicating)
FRN-R-(amp)ID (indicating)
Ratings:
Volts — 250Vac, 125Vdc
Amps
1
10-60 Amps
IR — 200kA Vac RMS Sym.
— 20kA Vdc
Agency Information:
CE, UL Listed, Std. 248-12, Class RK-5, Guide JDDZ,
File E4273
CSA Certified, C22.2 No. 248.12, Class 1422-02, File 53787
Catalog Numbers (amps) — Non-indictaing fuses
FRN-R-
1
10 FRN-R-1
8
10 FRN-R-8*
FRN-R-
1
8 FRN-R-2 FRN-R-9*
FRN-R-
15
100 FRN-R-2
1
4 FRN-R-10*
FRN-R-
2
10 FRN-R-2
1
2 FRN-R-12*
FRN-R-
1
4 FRN-R-2
8
10 FRN-R-15*
FRN-R-
3
10 FRN-R-3 FRN-R-17
1
2*
FRN-R-
4
10 FRN-R-3
2
10 FRN-R-20*
FRN-R-
1
2 FRN-R-3
1
2 FRN-R-25*
FRN-R-
6
10 FRN-R-4 FRN-R-30*
FRN-R-
8
10 FRN-R-4
1
2 FRN-R-35*
FRN-R-1 FRN-R-5 FRN-R-40*
FRN-R-1
1
8 FRN-R-5
6
10 FRN-R-45*
FRN-R-1
1
4 FRN-R-6 FRN-R-50*
FRN-R-1
4
10 FRN-R-6
1
4 FRN-R-60*
FRN-R-1
1
2 FRN-R-7
FRN-R-1
6
10 FRN-R-7
1
2
* Open fuse indication available by inserting the sufix “ID.” E.g., FRN-R-15ID.
Carton Quantity and Weight
Amp Rating Carton Qty.
1
10–15 10
17
1
2–30 10
35–60 10
D
imensions - in
Features:
Provides motor overload, ground fault and short-circuit
protection
Helps protect motors against burnout from overloads
Helps protect motors against burnout from single-phasing
on three-phase systems
Simplifies and improves blackout prevention
(selective coordination)
Dual-element fuses can be applied in circuits subject to
temporary motor overloads and surge currents to provide
both high performance short-circuit and overload
protection
The overload element provides protection against low level
overcurrent of overloads and will hold an overload which is
five times greater than the ampere rating of the fuse for a
minimum of ten seconds.
Recommended Fuse Blocks
Fuse Amps 1-Pole 2-Pole 3-Pole
0-30
H25030-1 H25030-2 H25030-3
R25030-1 R25030-2 R25030-3
35-60
H25060-1 H25060-2 H25060-3
R25060-1 R25060-2 R25060-3
For additional information on the 250 volt fuse blocks, see
Data Sheets # 1110 (R250), # 1112 (H250).
Fuse Reducers For Class R Fuses
Equipment Desired Fuse Catalog Numbers
Fuse Clips (Case) Size (Pairs) 250V
60A 30A NO.263-R
100A
30A NO.213-R
60A NO.216-R
200A 60A NO.226-R
For additional information on Class R fuse reducers, see
Data Sheet # 1118.
0
.56" (±0.008)
2
"
(
± 0.31)
1/10 to 30A
3"
35 to 60A
0
.81" (±0.008)
(
± 0.31)
0713 BU-SB13730 Page 2 of 3 Data Sheet # 1019
FUSETRON™ 250V Class RK5
T
ime-Current Curves - Average Melt
1
10 to 6
1
4 Amps
AMP RATING
CURRENT IN AMPS
TIME IN SECONDS
FRN-R — 250Vac/125Vdc,
1
10-60A, Dual Element, Time-Delay Fuses
0713 BU-SB13730 Page 3 of 3 Data Sheet # 1019
FUSETRON™ 250V Class RK5
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information
contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
C
urrent-Limitation CurvesTime-Current Curves - Average Melt
8 to 60 Amps
400000
9
000
8000
7000
7000
6
000
6000
300000
2
00000
1
00000
5
000
4
000
4000
9
0000
3
000
2
000
1
000
3000
70000
80000
7
0000
6
0000
B
A
5
0000
60000
200000
20000
2000
40000
100000
50000
10000
5000
1000
30000
90000
80000
4
0000
9000
8000
3
0000
2
0000
10000
3
0A
6
0A
AMP RATING
INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPS
PROSPECTIVE SHORT-CIRCUIT CURRENT - SYMMETRICAL RMS AMPS
FRN-R — 250Vac/125Vdc,
1
10-60A, Dual Element, Time-Delay Fuses
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information
contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
AMP RATING
CURRENT IN AMPS
TIME IN SECONDS
810 15 30 60
Current-Limiting Effects
Prosp. Let-Through Current
S.C.C. (Apparent RMS Symmetrical Vs. Fuse Rating)
30A 60A
5000 1000 2000
10,000 2000 3000
15,000 2000 3000
20,000 2000 4000
25,000 2000 4000
30,000 2000 4000
35,000 2000 4000
40,000 2000 5000
50,000 3000 5000
60,000 3000 5000
70,000 3000 6000
80,000 3000 6000
90,000 3000 6000
100,000 3000 6000
150,000 4000 7000