Magnetic and Hydraulic-Magnetic Circuit Breaker 8345-...
www.e-t-a.de
1651 1
1
Description
Typical applications
Technical data
Single or multipole hydraulic-magnetic circuit breakers with trip-free -
mechanism and toggle actuation. A choice of switching characteristics
ensures suitability for a wide range of applications. Industry standard
dimensions and panel mounting. Auxiliary contacts optional. Low
temperature sensitivity at rated load.
Approved to CBE standard EN 60934 (IEC 60934) S-type HM CBE.
In the business fields Communication and Transport: power supplies,
switchgear, instrumentation and process control engineering.
8345
1-pole 2-pole
Voltage rating 3 AC 415 V; AC 277/480 V;
AC 120/240 V; AC 240 V; DC 80 V
(higher DC voltages to special order)
Current rating range 0.05...125 A single and multipole
higher ratings upon request
Auxiliary circuit AC 240 V 6 A
DC 28 V 3 A
DC 65 V 1 A
DC 80 V 0.5 A
Typical life 10,000 operations at 1 x I
N
Ambient temperature -40...+85 °C (-40...+185 °F)
Insulation co-ordination
(IEC 60664) 2.5 kV/2
reinforced insulation in operating area
Dielectric strength
operating area test voltage AC 3,000 V
Line to Load test voltage AC 1,500 V
pole to pole
(2- and 3-pole) test voltage AC 1,500 V
main to auxiliary circuit test voltage AC 3,000 V
switching to trip circuit test voltage AC 1,500 V
(version -X)
Insulation resistance > 100 MΩ (DC 500 V)
Degree of protection operating area IP40
(IEC 60529) terminal area IP00
Vibration
upside down: 10 g (57-2000 Hz) ± 0,76 mm (10-57 Hz)
at 0.9 I
N
directions 1, 2, 3, 4, 5: 10 g at 1 x I
N
with curves F1, F2: 10 g at 0.8 x I
N
in all planes.
(57-2000 Hz) ± 0.76 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock
directions 1, 2, 3, 4, 5: 100 g (11 ms) at 1 x I
N
,
direction 6: 100 g (11 ms) at 0.8 x I
N
,
with curves F1, F2: 100 g (11 ms) at 0.8 x I
N
to IEC 60068-2-27, test Ea
Corrosion 96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH,
to IEC 60068-2-78, test Cab
Mass approx. 90 - 120 g per pole
depending on version
Standard current ratings and typical internal resistance values
Interrupting capacity
to EN 60934, CCC, UL 489, UL 1077
IEC 60934 / CCC (3-pole) – test series E:
voltage number of
poles
I
N
max. (A) I
cn
(A)
DC 80 V 1 + 2 0.02...125 10 000
AC 240/415 V 1 - (6) 0.02...80 6 x I
N
AC 240 V 1 0.02...20 5 000
UL 489 – test sequence Z:
voltage number of
poles
I
N
max. (A) I
cn
(A)
DC 80 V 1 + 2 0.5...125 10 000
AC 120 V 1 0.5...80 5 000
AC 120/240 V 1 (2) 0.5...80 5 000
AC 240 V 1 0.5...20 5 000
UL 1077:
voltage number of
poles
I
N
max. (A) I
cn
(A)
DC 80 V 1 + 2 0.02...125 10 000
AC 277/480 V 1 - 6 0.02...70 5 000
Current
rating (A)
Trip curves and internal resistance (Ω) per pole
F1 F2 K1, M1, T1 K2, M2, T2
0,05
275 152 531 542
0,1
58 36,5 129 127
1
0,578 0,347 1,10 1,08
2
0,144 0,0959 0,295 0,291
3
0,0644 0,0477 0,121 0,118
5
0,0250 0,0192 0,0437 0,0449
10
0,00901 0,00714 0,0147 0,0133
15
0,00597 0,00483 0,00794 0,00794
20
0,00468 0,00410 0,00597 0,00597
25
0,00410 0,00385 0,00456 0,00456
30
0,00385 0,00371 0,00458 0,00458
40
0,00371 0,00371 0,00373 0,00373
50
0,00358 0,00358 0,00335 0,00335
60
--- --- 0,00333 0,00333
80
--- --- 0,00325 0,00325
100
--- --- 0,00316 0,00316
125
--- --- 0,00314 0,00314