P O W E R T R A N S F O R M E R
CHASSIS MOUNT : Autotransformer
Web: www.TriadMagnetics.com
Phone 951-277-0757
Fax 951-277-2757
Publish Date: May 11, 2015
F-302U
Electrical Specifications (@25ºC)
1. Maximum Power: 150 VA
2. Input Voltage: 277 V, 60 Hz only
3. Output Voltage 115V, + 5% at full load
4. Full Secondary Load 1.3 Amps RMS
Construction:
Single winding on a double wall, nylon bobbin. Three leads exit the
transformer, the black lead is the tap.
Description:
Secondary coil is a fraction of the entire winding for voltage step-down.
This causes part of the power to be transferred conductively through the
windings, rather than all of the power being transferred by induction.
Safety:
These units are designed with 1500V isolation between the winding and the
core. Materials and construction are rated for Class B insulation system.
E50476
Dimensions: Unit: In inches
Mtg Slots: .203X.375 (4)
Schematic:
RoHS Compliance: As of manufacturing date February 2005, all standard products meet
the requirements of 2011/65/EU, known as the RoHS initiative.
* Upon printing, this document is considered “uncontrolled”. Please contact Triad
Magnetics’ website for the most current version.