159
SAK-series
Disconnect test terminal against induced high voltage
Measures to minimize risks of electric vol-
tage peaks in control systems of power
plants and transforming stations:
• Insulation between installation and con-
trol cable by pulling disconnect plugs.
• Grounding of control cable is possible on
an appropriate location of the workplace.
• Easy connection of electric isolation of
counting, control and communication cir-
cuits.
Electricity Supply Industry Standard
ESI 12-4 1973
The Electricity Supply Industry Standard
ESI 12-4 1973 defines a detailed specifica-
tion of control and protection equipment.
The main functions of thiese installations
are as follows:
• Insulation of the control cables located in
front of ground or installation lines with
increased potential, which is required to
prevent unintentional contact of service
staff with live parts.
• Separation of control cables from local
control circuits.
• Application also includes test connec-
tions for auxiliary control circuits and / or
local control circuits.
• Grounding of control cables and / or
auxiliary control circuits.
• Bundled disconnection of all auxiliary
control circuits from potential earth.
• A test voltage can be applied using the
screening connection of the control
cable, which is normally routed on the
enclosure, with the help of an appropria-
te separation. This permits to check
whether the screening line is correctly
functioning. For this test, an insulated
feed-through plate is required.
ESI 12-4:
"Terminating Equipment for Pilot Cables
subject to Induced Transient Voltages
exceeding 650 V rms".
SAKH 6
Y
15/138/79
12 mm
15 kV ac (ESI 12-4)**/30 A
0.5...10
0.5...10*
W Cat. No. Qty.
PPT/35 3835020000 10
incl. disconnect plug and dis-
placement tool (if min. 10
items are ordered)
AP/PPT (3) 3835120000 10
TST/PPT 3835360000 10
PH/PPT 3835260000 10
The disconnect plug may only
be removed with the displace-
ment tool.
PS (4) 0299600000 20
StB 17 0147100000 50
TSK 35 0514300000 1
DEK 5 see “Accessories”
12 mm
1 kV ac / 1.5 kV dc / 47 A
>15 kV (from terminal to terminal)
0.5... 6
0.5... 6
W Cat. No. Qty.
SAKH 6 0126600000 50
AP 0131700000 20
DEK 5 see “Accessories”
PPT/35
Dimensions/approvals
Width/length/height (mm) with TS 35 x 7.5 W
Insulation stripping length/clamping screw/screwdriver blade
Rated data according to IEC 60 947-7-1
Rated voltage/current
Rated impulse voltage/pollution severity
Clampable conductor
Solid H07V-U mm
2
Stranded H07V-R mm
2
Ordering data Version
EP
End plate
EP
Disconnect plug
Displacement tool
PA
Test plug/socket
Insulated mounting rail
PVC 35 x 1.5 mm
Marking tags Print
DEK Standard
Mounting rails, end brackets, further marking material see “Accessories”
* Also two push-on tabs are possible